1. Identify the Exact Battery
Record chemistry, model, capacity, nominal voltage and the manufacturer's storage instructions. “12V lithium” is not enough information because different chemistries and product designs can have different storage and charging limits.
If you are still comparing chemistries, the Lithium Battery Types Guide and LiFePO4 vs Li-ion comparison explain why storage behavior should be treated as product-specific rather than universal.
2. Set the Manufacturer-Approved SOC
Charge or discharge the battery to the storage condition specified in its manual. Avoid chasing a generic “perfect” percentage if your manufacturer gives a different instruction. If no storage SOC is published, contact the manufacturer or distributor rather than inventing a target.
Once the target is reached, record the date and measured SOC or open-circuit voltage. A simple storage log makes later checks more useful because you can see whether the battery is losing charge faster than expected.
3. Isolate Loads and Charging Sources
Turn off loads, solar input and chargers as required by the system manual, then verify whether any standby circuits remain connected. RVs, boats and solar systems often contain small always-on loads that are easy to miss.
- Check inverters, DC-DC chargers and solar controllers.
- Check shunts, alarms, trackers and communications devices.
- Use a real disconnect method approved for the system.
- Protect exposed terminals from accidental short circuits.
4. Store, Inspect and Recommission
Place the battery in a clean, dry, stable location within its published storage-temperature range. Keep it away from direct sunlight, heaters, water intrusion and objects that could damage the case or bridge the terminals.
At the inspection interval recommended by the manufacturer, check the enclosure, cables, terminals and state of charge. Before returning the battery to service, restore charging and loads in the correct order and verify that the BMS and system monitor report normal conditions.
Safety note: This Lithium Battery Storage Guide does not recommend storing any battery that is swollen, leaking, punctured, unusually hot, making abnormal noises or showing other signs of damage. NFPA consumer guidance advises keeping lithium-ion batteries away from combustible materials and following manufacturer instructions. For large stationary energy-storage systems, installation and storage requirements may also be governed by local electrical, fire and building codes.
The table below is a decision framework, not a set of universal numeric limits. The correct value in the “what to use” column is whatever your exact battery documentation specifies.
Simple arithmetic can expose hidden drain before storage. For a known standby current, convert milliamps to amps and multiply by time.
Stored capacity removed by parasitic loads (Ah) = standby current (mA ÷ 1000) × 24 × days
Projected SOC from parasitic load only (%) = starting SOC − [drained Ah ÷ rated Ah × 100]
Example: a 10mA standby load equals 0.01A. Over 120 days, 0.01 × 24 × 120 = 28.8Ah. On a 100Ah battery that started at 80% SOC, parasitic draw alone would reduce the theoretical charge from 80Ah to about 51.2Ah, or 51.2% SOC. Real results can differ because battery self-discharge, BMS consumption, temperature and SOC measurement error are not constant.