A battery label often emphasizes amp-hours, while appliances and inverters are usually discussed in watts. Those units describe different things. Amp-hours measure electrical charge capacity. Watt-hours describe energy. To estimate runtime, the first step is therefore to convert battery Ah into Wh using nominal battery voltage. If you need only that conversion, the Battery Ah to Wh Calculator provides a focused version of the same arithmetic.
Nominal Battery Energy (Wh) = Battery Capacity (Ah) × Nominal Voltage (V)
A 100Ah battery at 12.8V has 1,280Wh of nominal energy. A 200Ah battery at the same voltage has 2,560Wh. This is why an Ah number should not be interpreted without voltage when you are comparing stored energy. The broader Battery Capacity Calculator is useful when you want to compare Ah, Wh and kWh across several system voltages.
The next step applies planned depth of discharge. This is the percentage of nominal energy you intend to remove before recharging or leaving a reserve. At 90% planned DoD, a 1,280Wh battery contributes 1,152Wh of usable battery energy in the model.
Usable Battery Energy (Wh) = Nominal Wh × (Depth of Discharge ÷ 100)
Depth of discharge is not the same thing as conversion efficiency. The calculator keeps them separate. If a load is powered through an inverter, energy is lost during conversion. At 90% delivery efficiency, 1,152Wh becomes 1,036.8Wh available to the modeled load.
Delivered Load Energy (Wh) = Usable Wh × (Efficiency ÷ 100)
Finally, runtime is delivered watt-hours divided by the average load in watts. A steady 100W load supplied with 1,036.8Wh gives 10.368 hours. For a dedicated cross-check, use the Battery Runtime Calculator, which focuses specifically on runtime rather than the wider 12V planning workflow.
Runtime (hours) = Delivered Energy (Wh) ÷ Average Load (W)
The current estimate works in the other direction. For a simplified battery-side current calculation, load watts are divided by nominal voltage and delivery efficiency. At 100W, 12.8V and 90% efficiency, the model returns about 8.68A. That number helps show the scale of the load, but it does not replace a proper conductor or protection calculation. Use the site's Wire Gauge Calculator as a first voltage-drop check and then confirm the final circuit against the equipment instructions and applicable electrical requirements.